vi-VNen-US
Cabinet Acqui GXT3-48VBATT
Cabinet Acqui GXT3-48VBATT
GXT3-48VBATT
10.033.000 VND

Emerson Liebert® External battery cabinet with power capacity of 700 – 3000 VA outputs from Critical Power Supplies.

A constant voltage of 48 VDC. Battery cabinet is compatible with Liebert GxT3 series UPS system and uses SNMP network management system for remote monitoring.

Features and Benefits.

- Output voltage: 48 VDC
- Power capacity: 700 – 3000 VA
- Battery information: User replaceable hot swappable, Backup/run time(0.7 pf): 5 minutes, Rating: 9.0Ah
- Form factor: 2U
- Interface/ports: USB
- Network management: SNMP
- Features high ef?ciency at on line mode, rack/tower convertible with rotatable front panel, offers twice the reliability of line interactive UPSsystems, features longer lasting batteries than line interactive UPS systems
- Output power factor: 0.9
- Compatibility: Liebert GXT3 UPS series - Plug and play design
- Battery Type Valve Regulated Lead Acid
- Liebert External Battery Cabinet 48V for GXT3 700 to 2000 UPS. GXT3 700RT230, GXT3 1000RT230, GXT3 1500RT230, GXT3 2000RT230

Parameter

Model Number

GXT3-48VBATT

GXT3-72VBATT

 

Used w/UPS Model

GXT3-700RT230, GXT3-1000RT230, GXT3-1500RT230, GXT3-2000RT230

 

GXT3-3000RT230

Dimensions, D x W x H, mm (in)

Unit

497 × 430 × 85

19.7 x 16.9 x 3.3)

602 × 430 × 85

23.6 x 16.9 x 3.3)

Shipping

617 x 570 x 262

(24.3x 22.4 x 10.3)

717 x 570 x 262

(28.2 x 22.4 x 10.3)

Weight, kg (lb)

Unit

32 (70.5)

42 (92.6)

Shipping

35 (77.2)

46 (101.4)

Battery parameters

Type

Valve-regulated, nonspillable, lead acid

Qty × V× Rating

2 × 4 × 12V × 9.0Ah

2 × 6 × 12V × 9.0Ah

Battery Mfr/Part#

Panasonic/UP-RW1245 CSB/HR 1234W F2

Backup Time

-

Environmental

Operating Temperature

0ºC to 40ºC (32ºF to 104ºF)

Storage Temperature

-15ºC to +40ºC (19ºF to 104ºF)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000m (10,000 ft.) at 40ºC (104ºF) without derating

Storage Elevation

15000m (50,000 ft.) maximum

Agency

Safety

IEC/EN/AS 62040-1:2008, GS mark

RFI/EMI

FCC Part 15, Class A=CISPR22 Class B

Surge Immunity

IEC 62040-2 2nd Ed.: 2006

Transportation

ISTA Procedure 1A